Article - CS333136
Connecting to a Local SoftLogix Soft PLC
Modified: 02-Nov-2020
Applies To
- Kepware Server (formerly KEPServerEX) 5.19.467.0 to 6.8
- ThingWorx Kepware Server (legacy) 8.0 to 8.4
Description
Before attempting to connect Kepware's Allen-Bradley ControlLogix Ethernet Driver to a SoftLogix Soft PLC running on the same PC, users should ensure the following: RSLinx does not have any Ethernet drivers running on the PC. The EtherNet/IP Messaging Module software is installed in the SoftLogix virtual chassis. The Device ID is set to "< specific_IP_address_of_PC >, 1, < PLC_CPU_slot >" instead of "127.0.0.1, 1, < PLC_CPU_slot >". For example, if the PC's IP Address is "192.168.3.4" and the SoftLogix CPU is in slot 2 of the virtual chassis, then the Device ID should be set to "192.168.3.4,1,2". Note: To locate the Device ID setting in KEPServerEX, right-click on the device. Then, select Properties and open the General tab.