Article - CS338549
Automatic Tag Generation (ATG) fails in OPC UA Client driver with 0X80AD0000 in PTC Kepware Products
Modified: 10-Sep-2021
Applies To
- Kepware Server (formerly KEPServerEX) 6.0.2107.0 to 6.10
- ThingWorx Kepware Server (legacy) 8.0 to 6.10
Description
- Automatic Tag Generation (ATG) fails in OPC UA Client driver with 0X80AD0000 (UA_SCBADDISCONNECT)
- ATG fails when requesting tags from OPC UA server of an TP900 Comfort of Siemens
- Bad quality is read from OPC UA Server but Good quality is read for same tag with 3rd party OPC UA Client software like UaExpert
- Event log:
Warning OPC UA Client Unable to obtain data type information from server. Tags of some data types may not be imported.
Information KEPServerEX\Runtime Attempting to automatically generate tags for device
Warning OPC UA Client Unable to read tag attributes during import. Tag cannot be imported. | Tag name Status description = 'The server has disconnected from the client.', Status code = 0X80AD0000.
Information KEPServerEX\Runtime Completed automatic tag generation for device
Warning OPC UA Client Reconnecting server due to connection loss.
Information KEPServerEX\Runtime Attempting to automatically generate tags for device
Warning OPC UA Client Unable to read tag attributes during import. Tag cannot be imported. | Tag name Status description = 'The server has disconnected from the client.', Status code = 0X80AD0000.
Information KEPServerEX\Runtime Completed automatic tag generation for device
Warning OPC UA Client Reconnecting server due to connection loss.
This is a printer-friendly version of Article 338549 and may be out of date. For the latest version click CS338549