Article - CS333344
Omron FINS Ethernet Driver Displays "Device '<device name>' responded with write not possible (Tag '<tag name>', Size '<size>').[Main, Sub: '0x21, 0x08']" Error Message
Modified: 02-Nov-2020
Applies To
- Kepware Server (formerly KEPServerEX) 5.19.467.0 to 6.8
- ThingWorx Kepware Server (legacy) 8.0 to 8.4
Description
Possible Cause: This error may indicate that the controller's rotary switches are set incorrectly. Solution: Verify that the rotary switch labeled "UNIT No." is set for the Unit Number. Then, verify that the two rotary switches labeled "NODE No." are set for Node No (which is typically the same as the right-most octet of the device's IP address). Note: For more information, refer to Main and Sub Error Codes in the Omron FINS Ethernet help file.
This is a printer-friendly version of Article 333344 and may be out of date. For the latest version click CS333344