기술 문서 - CS307824
OPC UA Client driver fails to connect to OPC UA server in PTC Kepware Products
수정한 날짜: 08-May-2020
적용 대상
- KEPServerEX 6.6.350.0 N/A to 6.10.623.0
- ThingWorx Kepware Server 6.6.362.0 to 6.10.623.0
- Driver: OPC UA Client
설명
- Failure to connect to OPC UA server in KEPServerEX / ThingWorx Industrial Connectivity (KSE/TWIC)
- Error message in \ThingworxStorage\logs\EventLog.log:
OPC UA Client Channel failed to connect | Status: 'The endpoint is not supported by the server'
Warning OPC UA Client OPC Test UA | There is no exact match for the configured endpoint URL in the UA Server.
Warning OPC UA Client OPC Test UA | There is no exact match for the configured endpoint URL in the UA Server.
- The target server is behind a NAT (network address translation) firewall with port forwarding
- The servers require DisableDomainCheck=true in the client
이는 기술 문서 CS307824의 PDF 버전이며, 구 버전일 수 있습니다. 최신 버전 https://www.ptc.com/ko/support/article/cs307824